Fire pump control cabinet installation requirements

2024-07-17

According to the "Fire Water Supply andfire hydrantSystem Technical Specifications", today the editor will tell you about theFire pump control cabinetThe problem of setting requirements.


The fire control room or duty room should have the following control and display functions:Fire control cabinetOr the control panel should be equipped with a manual direct pump start button connected by special wiring.


  Fire pump control cabinetor the control panel should displayfire water pumpandStabilizer pumpThe operating status of the system should be able to display high and low water level warning signals and normal water levels of fire pools, high-level fire water tanks and other water sources.


whenFire pump control cabinetset in dedicatedfire water pumpWhen used in a control room, its protection level shall not be lower than IP30. When set withfire water pump, in the same space, its protection level shall not be lower than IP55.


The fire pump control cabinet should be equipped with a mechanical emergency pump starting function, and it should be ensured that faults in the control loop in the control cabinet are started by personnel with management authorityfire water pump. When starting a mechanical emergency, make surefire water pumpWorks normally within 5.0 minutes.


In order to ensure the reliability of the starting pump in the fire control room, regulationsfire water pumpDirect start-up should be done using hard cables to minimize interference and risk. If a weak current signal bus system is used for control, the software may not be able to run due to the risk of intrusion.


showfire pumpandStabilizer pumpThe purpose of monitoring their operation status is to ensure the reliability of fire water supply.


Firefighting requires fire water. Some fires cause disaster primarily because there is no water. For example, the fire water tank on the roof of an auto parts store in a provincial capital city burned down because there was no water, and the fire water tank in a furniture store burned down because there was no water. Therefore, when formulating specifications, it is necessary to

Test the water level of the source. When the water level drops or overflows, you can replenish water and repair the water inlet valve in time.