Recommended products
XBD-W horizontal fire pumpXBD-W horizontal fire pump
01

XBD-W horizontal fire pump

2024-09-10
Product introduction This product refers to the People's Republic of Chinafire pumpStandard GB6245-2006《fire pump"Performance Requirements and Test Methods", combined with the company's many years of practical production experience and designed with reference to modern excellent water conservancy models, specifically for fire protection systemscentrifugal pump, product performance has reached the advanced level of similar domestic products. The product has been type-tested by the National Fire Equipment Quality Supervision and Inspection Center, and all performance indicators have met the standard requirements. It has obtained the "Fire Protection Product Certification Certificate" issued by the Fire Protection Product Conformity Assessment Center of the Ministry of Emergency Response.
? ?
Parameter description

Flow range of conveyed liquid:1~120L/S

Lift range:30~160m

Supporting power range:1.5~200KW

Rated speed:2900r/min, 2850r/min

? ?
working conditions Medium temperature:The ambient temperature of -15℃-80℃ is not greater than 40℃, and the relative humidity is less than 95%; it can transport clean water or non-corrosive media with physical and chemical properties similar to clean water, and its solid insoluble matter does not exceed 0.1%.
? ?
Features

Smooth operation---Motor andpumpCoaxial, smooth operation, low noise, small vibration, high component concentricity;

Sealed and wear-resistant---Adopts carbide mechanical seal, which is wear-resistant, has long operating life, and has no pool leakage to ensure a clean environment;

Easy to install---The inlet and outlet diameters are the same, the center height is consistent, and installation is easy;

Any connection---pumpThe bottom of the body is equipped with a base and bolt holes for any rigid connection or flexible connection;

Complete exhaust---Set up a bleed valve to completely drainpumpair inside, make surepumpof normal startup.

? ?
Application areas Mainly used forFirefightingSystem pipelinePressurized water delivery. It can also be applied to industrial and urban water supply and drainage, and high-rise buildings.Pressurized water delivery, long-distance water supply, heating, bathroom, boiler hot and cold water circulation and pressurization, air conditioning and refrigeration system water supply and equipment supporting and other occasions.
Inquiry
view detail
XBD vertical fire pumpXBD vertical fire pump
01

XBD vertical fire pump

2024-09-10
Product introduction This product refers to the People's Republic of Chinafire pumpAccording to the provisions of the standard GB6245-2006 "Fire Pump Performance Requirements and Test Methods", it is designed based on the company's many years of practical production experience and with reference to modern excellent water conservancy models. It is specially used for fire protection systems.centrifugal pump, product performance has reached the advanced level of similar domestic products. The product has been type-tested by the National Fire Equipment Quality Supervision and Inspection Center, and all performance indicators have met the standard requirements. It has obtained the "Fire Protection Product Certification Certificate" issued by the Fire Protection Product Conformity Assessment Center of the Ministry of Emergency Response.
? ?
Parameter description

Flow range of conveyed liquid:1~120L/S

Lift range:30~160m

Supporting power range:1.5~200KW

Rated speed:2900r/min, 2850r/min

? ?
working conditions Medium temperature:The ambient temperature of -15℃-80℃ is not greater than 40℃, and the relative humidity is less than 95%; it can transport clean water or non-corrosive media with physical and chemical properties similar to clean water, and its solid insoluble matter does not exceed 0.1%.
? ?
Features

Smooth operation---The motor and the pump are coaxial, running smoothly, with low noise and vibration, and high component concentricity;

Sealed and wear-resistant---Adopts carbide mechanical seal, which is wear-resistant, has long operating life, and has no pool leakage to ensure a clean environment;

Easy to install---The inlet and outlet diameters are the same, the center height is consistent, and installation is easy;

arbitrary join---The bottom of the pump body is equipped with a base and bolt holes for any rigid connection or flexible connection;

Complete exhaust--- Set up a bleed valve to completely drain the air in the pump to ensure normal startup of the pump.

? ?
Application areas Mainly used forFirefightingThe system pipeline pressurizes and delivers water. It can also be used in industrial and urban water supply and drainage, pressurized water supply in high-rise buildings, long-distance water supply, heating, bathrooms, boiler hot and cold water circulation pressurization, air conditioning and refrigeration system water supply and equipment matching, etc.
Inquiry
view detail
XBD-QYSJ long axis deep well fire pumpXBD-QYSJ long axis deep well fire pump
01

XBD-QYSJ long axis deep well fire pump

2024-09-10
Product introduction Sham Tseng Fire Pump UnitAccording to the People's Republic of Chinafire pumpStandard GB6245-2006《fire pumpPerformance Requirements and Test Methods" developedfire pump unit. The product has been type-tested by the China Fire Equipment Quality Supervision and Testing Center, and all performance indicators have met the standard requirements, and it has obtained a fire product approval certificate.
? ?
Parameter description

Flow range of conveyed liquid:5~100L/S

Lift range:32~200m

Supporting power range:3~200KW

Rated speed:2900r/min

? ?
working conditions The rated frequency is 50 Hz, and the rated voltage at the motor end should be guaranteed to be 380±5% of the three-phase AC power supply; the load power of the transformer should not exceed 75% of its capacity; generally non-corrosive clean water, and the solid content (by weight) in the water should not Greater than 0.01%; the water temperature should not be higher than 40°C, the pH value should be within the range of 6.5 to 8.5, and the hydrogen sulfide content should not be greater than 1.5 mg/L.
? ?
Features Sham Tseng Fire Pump UnitIt consists of multiple centrifugal impellers and guide shells, water pipes, drive shafts,pumpIt is composed of base, motor and other components.pumpThe seat and motor are located above the pool. The power of the motor is transmitted to the impeller shaft through the rotating shaft concentric with the water pipe, thereby generating flow and pressure.
? ?
Application areas Sham Tsui Fire PumpMainly used in fixed firefighting systems in industrial and mining enterprises, engineering construction, high-rise buildings, etc.fire hydrantFire extinguishing, automatic sprinkler fire extinguishing and other fire extinguishing systems can be used to transport clean water without solid particles and media with chemical properties similar to water. They can also be used in shared water supply systems for living and production, as well as construction and municipal water supply and drainage.
Inquiry
view detail
XBD-S horizontal split double suction fire pumpXBD-S horizontal split double suction fire pump
01

XBD-S horizontal split double suction fire pump

2024-09-10
Product introduction Horizontal split double suction fire pumpIt's all onepumpThe new type developed by the industrial group by introducing advanced German technology and new standardsfire pump unitThe product mainly achieves high efficiency, full and broad spectrum by improving the impeller condition.Horizontal split double suction fire pumpAn electric motor can be used as the driving form. This series ofwater pumpIt can meet the requirements in terms of performance, structure, materials and supporting facilities.fire pumpRequire.
? ?
Parameter description

Flow range of conveyed liquid:5~500L/s

Lift range:15~160m

Supporting power range:30~400kw

Rated speed:1450~2900r/min

? ?
working conditions The medium weight does not exceed 1240kg/m°; the ambient temperature is ≤50℃, the medium temperature is ≤80℃, and special requirements can reach 200℃: the medium PH value is cast iron material of 6~9, stainless steel is 2~13; the self-priming height cannot exceed 4.5 ~5.5 meters, the length of the suction pipe is ≤10 meters; the rotation speed is generally 1450r/min~3000r/min.
? ?
Application areas XBD-QYS typeDiesel engine fire pump unitIt is in accordance with the standard GB6245-2006fire pumpPerformance Requirements and Test Methods". This series of products has a wide range of lift and flow, which can fully meet the needs of various industrial and mining enterprises such as warehouses, docks, airports, petrochemicals, power plants, liquefied gas stations, and textiles.fire water supply.
Inquiry
view detail
XBC-QYW single-stage diesel engine fire pump setXBC-QYW single-stage diesel engine fire pump set
01

XBC-QYW single-stage diesel engine fire pump set

2024-09-10
Product introduction

Control mode:Manual/automatic and remote control functions support manual control, automatic control, and remote control of the start and stop of the water pump, and the control mode can be switched;

Time setting:The control time of the diesel engine can be set, including: start delay time, preheating or pre-tuning time, start cutoff time, speed at start cutoff, rapid running time, speed-up process time, cooling stop time;

Alarm shutdown:Automatic alarm and shutdown items: no speed signal, overspeed, low speed, low oil pressure, high cooling temperature, start failure, shutdown failure, oil pressure sensor open circuit/short circuit, water temperature sensor open circuit/short circuit, speed sensor open circuit/short circuit,water pumpWater pressure is too low, etc.;

Early warning items:Pre-alarm items: overspeed, low speed, low oil pressure, high cooling temperature, low temperature, low fuel level, low battery voltage. High battery voltage, uncalibrated speed signal and low water pump pressure, etc.; status display:

Status display:Diesel engine operating status display: According to the current actual situation of the system, the current status of the equipment is displayed: waiting, starting, fuel supply, starting, starting delay, rapid delay, normal operation, clean shutdown, emergency shutdown;

Parameter display:Diesel engine parameter measurement display: During system operation, the current relevant parameter values ??are displayed: rotation speed, running time, fuel volume, battery voltage, cooling temperature, and oil pressure.

? ?
Parameter description

Flow range of conveyed liquid:5~500L/s

Lift range:15~160m

Supporting power range:30~400kw

Rated speed:1450~2900r/min

? ?
working conditions The medium weight does not exceed 1240kg/m°; the ambient temperature is ≤50°C, the medium temperature is ≤80°C, and special requirements can reach 200°C; the medium PH value of cast iron is 6~9, stainless steel is 2~13; the self-priming height cannot exceed 4.5 ~5.5 meters, the length of the suction pipe is ≤10 meters: the rotation speed is generally 1450r/min~3000r/min.
? ?
Application areas XBC-QYW typeDiesel engine fire pump unitIn accordance with the standard GB6245-20 "Fire Pump Performance Requirements and Test Methods", this series of products has a wide range of head and flow, and can fully meet various occasions in industrial and mining enterprises such as warehouses, docks, airports, petrochemicals, power plants, liquefied gas stations, and textiles. fire water supply. The advantage is that the electric fire pump cannot be started after a sudden power outage in the building's electrical system, and the diesel fire pump automatically starts and puts into emergency water supply.
Inquiry
view detail
XBD-CDL multi-stage fire pump booster and voltage stabilizing supporting solutionXBD-CDL multi-stage fire pump booster and voltage stabilizing supporting solution
01

XBD-CDL multi-stage fire pump booster and voltage stabilizing supporting solution

2024-09-10
Product introduction This product refers to the People's Republic of Chinafire pumpAccording to the provisions of the standard GB6245-2006 "Fire Pump Performance Requirements and Test Methods", combined with the company's many years of production practical experience, it is designed with reference to modern excellent water conservancy models. It is specially used for the heart pump of the fire protection system. The product performance reaches the same level as domestic similar products. advanced level. The product passed the type test of the National Fire Equipment Quality Supervision and Inspection Center, and all performance indicators met the standard requirements. It was awarded the "Fire Protection Product Certification Certificate" issued by the Fire Protection Product Conformity Assessment Center of the Ministry of Emergency Management.
? ?
Parameter description

Flow range of conveyed liquid:1~5/s

Lift range:30~150m

Supporting power range:0.75~18.5

Rated speed:2900r/min

Material:Tank and pipeline carbon steel, ball sleeve pump body, stainless steel impeller, stainless steel shaft

? ?
working conditions

The equipment canfire water supplyThe most unfavorable point of the pipeline system always maintains fire pressure, and uses the 30-second fire water volume always stored in the pneumatic water tank to ensurefire pumpFire sprinkler water before operation;

This equipment uses the operating pressure set by the pneumatic water tank to control the operating conditions of the water pump to achieve the function of boosting and stabilizing pressure;

●P1 (MPa) The most unfavorable point always maintains the pressure required for fire protection:

●P2 (MPa) fire pump starting pressure;

●PS1 (MPa) stabilizes the pump starting pressure;

●PS2 (MPa) stabilizes the pump stop pressure.

Inquiry
view detail
XBD-L single-stage fire pump booster and voltage stabilizing supporting solutionXBD-L single-stage fire pump booster and voltage stabilizing supporting solution
01

XBD-L single-stage fire pump booster and voltage stabilizing supporting solution

2024-09-10
Product introduction This product refers to the People's Republic of Chinafire pumpStandard GB6245-2006《fire pump"Performance Requirements and Test Methods", combined with the company's many years of practical production experience and designed with reference to modern excellent water conservancy models, specifically for fire protection systemscentrifugal pump, product performance has reached the advanced level of similar domestic products. The product passed the type test of the National Fire Equipment Quality Supervision and Inspection Center, and all performance indicators met the standard requirements. It was awarded the "Fire Protection Product Certification Certificate" issued by the Fire Protection Product Conformity Assessment Center of the Ministry of Emergency Management.
? ?
Parameter description

Flow range of conveyed liquid:1~5/s

Lift range:30~150m

Supporting power range:0.75~18.5

Rated speed:2900r/min

Material:Tank and pipeline carbon steel, ball sleeve pump body, stainless steel impeller, stainless steel shaft

? ?
working conditions

The equipment canfire water supplyThe most unfavorable point of the pipeline system always maintains fire pressure, and uses the 30-second fire water volume always stored in the pneumatic water tank to ensurefire pumpbefore runningfire sprinkleruse water;

This equipment uses the operating pressure set by the pneumatic water tank to controlwater pumpoperating conditions, reachingBoost and stabilize voltagefunction;

●P1 (MPa) The most unfavorable point always maintains the pressure required for fire protection:

●P2(MPa)fire pumpPump starting pressure;

●PS1(MPa)Stabilizer pumpPump starting pressure;

●PS2(MPa)Stabilizer pumpStop pump pressure.

Inquiry
view detail
XBD-CDL vertical multi-stage fire-fighting voltage stabilizing pumpXBD-CDL vertical multi-stage fire-fighting voltage stabilizing pump
01

XBD-CDL vertical multi-stage fire pressure regulator pump

2024-09-10
Product introduction Vertical multi-stage fire pump unit,Vertical multi-stage fire-fighting voltage stabilizing pump unitis with reference to the People's Republic of Chinafire pumpStandard GB6245-2006《fire pump"Performance Requirements and Test Methods", combined with the company's many years of practical production experience and designed with reference to modern excellent water conservancy models, specifically for fire protection systemscentrifugal pump, product performance has reached the advanced level of similar domestic products. The product has been type-tested by the National Fire Equipment Quality Supervision and Inspection Center, and all performance indicators have met the standard requirements. It has obtained the "Fire Protection Product Certification Certificate" issued by the Fire Protection Product Conformity Assessment Center of the Ministry of Emergency Management.
? ?
Parameter description

Flow range of conveyed liquid:1~50L/S

Lift range:30~220m

Supporting power range:0.45~160KW

Rated speed:2900r/min, 2850r/min

? ?
working conditions Medium temperature:The ambient temperature of -15℃-80℃ is not greater than 40℃, and the relative humidity is less than 95%; it can transport clean water or non-corrosive media with physical and chemical properties similar to clean water, and its solid insoluble matter does not exceed 0.1%.
? ?
Features

Vertical structure---BookpumpIt is a vertical, multi-level segmented structure.pumpThe inlet and outlet flanges are on the same horizontal axis and have the same diameter, which facilitates pipeline connection and is extremely convenient for loading and unloading;

Hydraulic balance---The impeller adopts hydraulic balancing method to balance the axial forcepumpThere is a guide bearing at the lower end, the shaft is fixedly driven through the clamp coupling and the motor shaft, and the outer cylinder is a stainless steel cylinder;

Sealing is reliable---The shaft seal adopts carbide mechanical seal, which has no leakage and no wear on the shaft, ensuring a clean working environment;

Extend life---The impeller and rotating friction parts are made of alloy, which is corrosion-resistant and rust-free. At the same time, it can avoid the generation of water and blockage of sprinklers and other fire-fighting devices, extending the service life.pumpservice life;

Hydraulic balance---Vertical multi-stage fire pressure stabilizing pumpLooking from the direction of the motor end,pumpFor counterclockwise rotation;Vertical multi-stage fire pumpViewed from the motor end, the pump rotates clockwise.

? ?
Application areas Mainly used for fire protection system pipesPressurized water delivery. It can also be used in industrial and urban water supply and drainage, pressurized water supply in high-rise buildings, long-distance water supply, heating, bathrooms, boiler hot and cold water circulation pressurization, air conditioning and refrigeration system water supply and equipment matching, etc.
Inquiry
view detail
XBD-GDL vertical multi-stage fire pumpXBD-GDL vertical multi-stage fire pump
01

XBD-GDL vertical multi-stage fire pump

2024-09-10
Product introduction Vertical multi-stage fire pump unit,Vertical multi-stage fire-fighting voltage stabilizing pump unitis with reference to the People's Republic of Chinafire pumpStandard GB6245-2006《fire pump"Performance Requirements and Test Methods", combined with the company's many years of practical production experience and designed with reference to modern excellent water conservancy models, specifically for fire protection systemscentrifugal pump, product performance has reached the advanced level of similar domestic products. The product has been type-tested by the National Fire Equipment Quality Supervision and Inspection Center, and all performance indicators have met the standard requirements. It has obtained the "Fire Protection Product Certification Certificate" issued by the Fire Protection Product Conformity Assessment Center of the Ministry of Emergency Management.
? ?
Parameter description

Flow range of conveyed liquid:1~50L/S

Lift range:30~220m

Supporting power range:0.45~160KW

Rated speed:2900r/min, 2850r/min

? ?
working conditions Medium temperature:The ambient temperature of -15℃-80℃ is not greater than 40℃, and the relative humidity is less than 95%; it can transport clean water or non-corrosive media with physical and chemical properties similar to clean water, and its solid insoluble matter does not exceed 0.1%.
? ?
Features

Vertical structure---BookpumpIt is a vertical, multi-level segmented structure.pumpThe inlet and outlet flanges are on the same horizontal axis and have the same diameter, which facilitates pipeline connection and is extremely convenient for loading and unloading;

Hydraulic balance---The impeller adopts hydraulic balancing method to balance the axial forcepumpThere is a guide bearing at the lower end, the shaft is fixedly driven through the clamp coupling and the motor shaft, and the outer cylinder is a stainless steel cylinder;

Sealing is reliable---The shaft seal adopts carbide mechanical seal, which has no leakage and no wear on the shaft, ensuring a clean working environment;

Extend life---The impeller and rotating friction parts are made of alloy, which is corrosion-resistant and rust-free. At the same time, it can avoid the generation of water and blockage of sprinklers and other fire-fighting devices, extending the service life.pumpservice life;

Hydraulic balance---Vertical multi-stage fire pressure stabilizing pumpLooking from the direction of the motor end,pumpFor counterclockwise rotation;Vertical multi-stage fire pumpLooking from the direction of the motor end,pumpfor clockwise rotation.

? ?
Application areas Mainly used for fire protection system pipesPressurized water delivery. It can also be applied to industrial and urban water supply and drainage, and high-rise buildings.Pressurized water delivery, long-distance water supply, heating, bathroom, boiler hot and cold water circulation and pressurization, air conditioning and refrigeration system water supply and equipment supporting and other occasions.
Inquiry
view detail
XBD-L-CDL main pump + multi-stage voltage stabilizing pump skid-mounted integrated pump unitXBD-L-CDL main pump + multi-stage voltage stabilizing pump skid-mounted integrated pump unit
01

XBD-L-CDL main pump + multi-stage voltage stabilizing pump skid-mounted integrated pump unit

2024-09-10
Product introduction This product refers to the People's Republic of Chinafire pumpStandard GB6245-2006《fire pump"Performance Requirements and Test Methods", combined with the company's many years of practical production experience and designed with reference to modern excellent water conservancy models, it is specially used for heart pumps in fire protection systems. The product performance has reached the advanced level of similar domestic products. The product passed the type test of the National Fire Equipment Quality Supervision and Inspection Center, and all performance indicators met the standard requirements. It was awarded the "Fire Protection Product Certification Certificate" issued by the Fire Protection Product Conformity Assessment Center of the Ministry of Emergency Management.
? ?
Parameter description

Flow range of conveyed liquid:1~5/s

Lift range:30~150m

Supporting power range:0.75~18.5

Rated speed:2900r/min

Material:Tank and pipeline carbon steel, ball sleeve pump body, stainless steel impeller, stainless steel shaft

? ?
working conditions

The equipment canfire water supplyThe most unfavorable point of the pipeline system always maintains fire pressure, and uses the 30-second fire water volume always stored in the pneumatic water tank to ensurefire pumpbefore runningfire sprinkleruse water;

This equipment uses the operating pressure set by the pneumatic water tank to controlwater pumpoperating conditions, reachingBoost and stabilize voltagefunction;

●P1 (MPa) The most unfavorable point always maintains the pressure required for fire protection:

●P2(MPa)fire pumpPump starting pressure;

●PS1(MPa)Stabilizer pumpPump starting pressure;

●PS2(MPa)Stabilizer pumpStop pump pressure.

Inquiry
view detail
XBC electric + backup diesel engine dual power skid-mounted fire pump setXBC electric + backup diesel engine dual power skid-mounted fire pump set
01

XBC electric + backup diesel engine dual power skid-mounted fire pump set

2024-09-10
Product introduction

Control mode:Manual/automatic, remote control functions support manual control, automatic control, and remote controlwater pumpThe start, stop and control modes can be switched;

Time setting:The control time of the diesel engine can be set, including: start delay time, preheating or pre-tuning time, start cut-off time, start-cut speed, rapid running time, speed-up process time, cooling down time;

Alarm shutdown:Automatic alarm and shutdown items: no speed signal overspeed, low speed, low oil pressure, high cooling temperature, start failure, shutdown failure, oil pressure sensor open circuit/short circuit, water temperature sensor open circuit/short circuit, speed sensor open circuit/short circuitwater pumpWater pressure is too low, etc.;

Early warning items:Pre-alarm items: over speed, low speed, low oil, high cooling temperature, low temperature, low fuel level, low battery voltage, high battery voltage, speed signal is not calibrated andpumpWater pressure is too low, etc.

Status display:Diesel engine operating status display: According to the current actual situation of the system, the current status of the equipment is displayed: waiting, engine, fuel supply, start, start delay, rapid delay, normal operation, clean shutdown, emergency shutdown;

Parameter display:Diesel engine parameter measurement display: During system operation, the current relevant parameter values ??are displayed: rotation speed, running time fuel volume, battery voltage, cooling temperature, and oil pressure.

? ?
Parameter description

Flow range of conveyed liquid:5~500L/s

Lift range:15~160m

Supporting power range:28~1150kw

Rated speed:1450~2900r/min

? ?
working conditions

The medium weight does not exceed 1240kg/m';
The ambient temperature is

The self-priming height cannot exceed 4.5~5.5 meters, and the length of the suction pipe is

The rotation speed is generally 1450r/min~3000r/min.

? ?
Application areas

XBC-QYS typeDiesel engine fire pump unitIt is in accordance with the standard requirements and test methods. The B6245-2006《fire pumpThe performance series products have a wide range of lift and flow, which can fully meet the requirements of various occasions such as warehouse factories, liquefied gas stations, textile and other terminals, airports, petrochemical, electrical and mining enterprises.fire water supply. The advantage is that the building is protectedpumpUnable to start, after the diesel engine power system suddenly loses powerElectric fire pumpAutomatically start investmentemergency water supply.

Inquiry
view detail
XBC diesel engine fire pump heat exchange modelXBC diesel engine fire pump heat exchange model
01

XBC diesel engine fire pump heat exchange model

2024-09-10
Product introduction

Control mode:Manual/automatic, remote control functions support manual control, automatic control, and remote controlwater pumpThe start, stop and control modes can be switched;

Time setting:The control time of the diesel engine can be set, including: start delay time, preheating or pre-tuning time, start cut-off time, start-cut speed, rapid running time, speed-up process time, cooling down time;

Alarm shutdown:Automatic alarm and shutdown items: no speed signal overspeed, low speed, low oil pressure, high cooling temperature, start failure, shutdown failure, oil pressure sensor open circuit/short circuit, water temperature sensor open circuit/short circuit, speed sensor open circuit/short circuitwater pumpWater pressure is too low, etc.;

Early warning items:Pre-alarm items: over speed, low speed, low oil, high cooling temperature, low temperature, low fuel level, low battery voltage, high battery voltage, speed signal is not calibrated andpumpWater pressure is too low, etc.

Status display:Diesel engine operating status display: According to the current actual situation of the system, the current status of the equipment is displayed: waiting, engine, fuel supply, start, start delay, rapid delay, normal operation, clean shutdown, emergency shutdown;

Parameter display:Diesel engine parameter measurement display: During system operation, the current relevant parameter values ??are displayed: rotation speed, running time fuel volume, battery voltage, cooling temperature, and oil pressure.

? ?
Parameter description

Flow range of conveyed liquid:5~500L/s

Lift range:15~160m

Supporting power range:28~1150kw

Rated speed:1450~2900r/min

? ?
working conditions

The medium weight does not exceed 1240kg/m';
The ambient temperature is

The self-priming height cannot exceed 4.5~5.5 meters, and the length of the suction pipe is

The rotation speed is generally 1450r/min~3000r/min.

? ?
Application areas

XBC-QYS typeDiesel engine fire pump unitIt is in accordance with the standard requirements and test methods. The B6245-2006《fire pumpThe performance series products have a wide range of lift and flow, which can fully meet the requirements of various occasions such as warehouse factories, liquefied gas stations, textile and other terminals, airports, petrochemical, electrical and mining enterprises.fire water supply. The advantage is that the building's anti-pump cannot be started and the diesel engine power system suddenly loses power.Electric fire pumpAutomatically activate emergency water supply.

Inquiry
view detail
XBD-2L-4 pressure direct start control cabinetXBD-2L-4 pressure direct start control cabinet
01

XBD-2L-4 pressure direct start control cabinet

2024-09-10
Product introduction Liquid level control cabinetFully absorb domestic and foreignwater pumpAdvanced control experience, after years of production and application, continuous improvement and optimization, it is carefully designed and manufactured.
? ?
Parameter description

Control motor power:0.75~22KW

Control voltage:380V

frequency:50HZ

controlwater pumpQuantity:1~4 units

? ?
Application areas For various occasions, such as domestic water supply and drainage,Firefighting, spraying, boosting, air conditioning cooling cycle, industrial control pumps,sewage dischargeThere are corresponding special model specifications.
? ?
Features Liquid level control cabinetWhen the liquid level in the sewage pool reaches the detection high level, current flows through the deep end of the electrode, and the signal is input to the control circuit and drives the switch circuit.sewage pumpStart the sewage discharge. When the liquid level is lower than the lower detection level, the input signal is interrupted.sewage pumpWhen the power is off and the sewage discharge is completed, it can also be directly controlled by manual gear. The control circuit is stable and liquid level ripples will not affect the output circuit.
Inquiry
view detail
XBD liquid level directly activates the control cabinetXBD liquid level directly activates the control cabinet
01

XBD liquid level directly activates the control cabinet

2024-09-10
Product introduction Liquid level control cabinetFully absorb domestic and foreignwater pumpAdvanced control experience, after years of production and application, continuous improvement and optimization, it is carefully designed and manufactured.
? ?
Parameter description

Control motor power:0.75~22KW

Control voltage:380V

frequency:50HZ

controlwater pumpQuantity:1~4 units

? ?
Application areas For various occasions, such as domestic water supply and drainage,Firefighting, spraying, boosting, air conditioning cooling cycle, industrial control pumps,sewage dischargeThere are corresponding special model specifications.
? ?
Features Liquid level control cabinetWhen the liquid level in the sewage pool reaches the detection high level, current flows through the deep end of the electrode, and the signal is input to the control circuit and drives the switch circuit.sewage pumpStart the sewage discharge. When the liquid level is lower than the lower detection level, the input signal is interrupted, the sewage pump is powered off, and the sewage discharge ends. It can also be directly controlled by manual gear. The control circuit is stable and liquid level ripples will not affect the output circuit.
Inquiry
view detail
QYK-XJ-132 QYK-XJ-132 6 fire-fighting auto-coupling step-down control cabinet 6 fire-fighting auto-coupling step-down control cabinetQYK-XJ-132 QYK-XJ-132 6 fire-fighting auto-coupling step-down control cabinet 6 fire-fighting auto-coupling step-down control cabinet
01

QYK-XJ-132 QYK-XJ-132 6 fire-fighting auto-coupling step-down control cabinet 6 fire-fighting auto-coupling step-down control cabinet

2024-09-10
Product introduction sinceCoupled pressure reduction start control cabinetIt is the company that fully absorbs domestic and foreignwater pumpAdvanced experience in control, after years of continuous improvement and optimization in production and application, it is carefully designed and manufactured. JJIAuto-decompression start control cabinetThe product has overload, short circuit, phase loss protection andpumpVarious protection functions such as body leakage, motor over-temperature and current leakage, complete status display, and singlepumpand morepumpControl working mode, multiple main and backup modespumpSwitching modes and various starting modes.
? ?
Parameter description

Control motor power:15~250KW

Control voltage:380V

controlwater pumpQuantity:1~4 units

? ?
Application areas Automatic control of domestic and industrial water supply and drainage,Firefighting, spray andbooster pumpAutomatic control, air conditioning hot and cold watercirculation pumpsystem, control and starting of other AC motors.
? ?
Features Auto-decompression start control cabinetIt is suitable for infrequent step-down starting of three-phase squirrel-cage induction motors with AC 50Hz, rated voltage 380V, and power of 11kW~400kW. The autotransformer's step-down characteristics are used to reduce the starting current to reduce the impact on the transmission network when the motor is started. influence.